LME39. Programmable controller
1. LMME39 is used for debugging and monitoring of 1st or 2nd stage gas burners or gas burners with intermittent operation mode
2. Flame monitoring is carried out through the flame detector QRA equipped with ion rods or auxiliary equipment AGQ3. xA27 specifically designed for gas blast burners.
Product features
1. Low voltage detection
2. Wind pressure monitoring is carried out by detecting the function of the air pressure switch during startup and operation
3. Remote reset of electronic control
4. Multi color indicator lights for faults and operational warnings
5. Recurrent limit
6. Calculate accurate program time through a digital signal processing system
7. Force intermittent operation after a maximum of 24 hours of uninterrupted operation
8. BCI interface
Specification parameters
Working voltage AC230V, -15% 6/+10% 6
Electric power consumption 12VA
Protection category I
Protection level IP40
Software level C complies with DIN EN 60730-2-5:2011 2-channel structure
The maximum input current of terminal 12 is 5A
Working environment operating standard DIN EN 60721-3-3
Climate condition level 3K3
Mechanical condition level 3M3
Temperature range -20...+60 ℃ C
Humidity<95% r. F
Weighing approximately 160g
250.000 starts in normal operating mode with a lifespan