LiYcY Cable PVC |
|
Application |
For signal and control cable in electronics of computer systems, electronic control equipment, office machine or process control units, which requires protection from electromagnetic interference (EMI) and electromagnetic radiation (EMR). |
|
Constructions |
1. Conductor: Class 5 Oxygen Free Copper |
2. Insulation: PVC |
3. Identification: Colored |
4. Screen: Tinned Copper Wire Braided |
5. Sheath: PVC |
|
Installation Temperature: Above 0ºC |
Operating Temperature: -15ºC ~ 70ºC |
|
Reference Standards |
VDE 0812 |
DIN 1704 |
VDE 0207 |
RoHS Directives |
IEC60332-1 |
|
Section Area | Rated Voltage | Test Voltage | Min. Insulation Resistance at 20ºC (MΩ/km) |
0.14~0.34mm2 | 250/250V | 1.2kV | 200 |
0.5~0.75mm2 | 300V | 2000V | 200 |
1.0~1.5mm2 | 300/500V | 3000V | 200 |
|
0.14mm2 |
No. of Cores | Conductor Construction (mm) | Insulation Thickness (mm) | Sheath Thickness (mm) | Overall Diameter (mm) | Max. DCR at 20ºC (Ω/km) |
2 | 12/0.12 | 0.35 | 0.7 | 4.4 | 148 |
3 | 12/0.12 | 0.35 | 0.7 | 4.7 | 148 |
4 | 12/0.12 | 0.35 | 0.7 | 4.9 | 148 |
5 | 12/0.12 | 0.35 | 0.7 | 5.3 | 148 |
7 | 12/0.12 | 0.35 | 0.7 | 5.6 | 148 |
8 | 12/0.12 | 0.35 | 0.8 | 6.2 | 148 |
10 | 12/0.12 | 0.35 | 0.8 | 7 | 148 |
12 | 12/0.12 | 0.35 | 0.8 | 7.3 | 148 |
14 | 12/0.12 | 0.35 | 0.8 | 7.5 | 148 |
|
0.25mm2 |
No. of Cores | Conductor Construction (mm) | Insulation Thickness (mm) | Sheath Thickness (mm) | Overall Diameter (mm) | Max. DCR at 20ºC (Ω/km) |
2 | 14/0.15 | 0.4 | 0.7 | 4.8 | 79.9 |
3 | 14/0.15 | 0.4 | 0.7 | 5.1 | 79.9 |
4 | 14/0.15 | 0.4 | 0.7 | 5.4 | 79.9 |
5 | 14/0.15 | 0.4 | 0.7 | 5.8 | 79.9 |
7 | 14/0.15 | 0.4 | 0.8 | 6.4 | 79.9 |
8 | 14/0.15 | 0.4 | 0.8 | 6.8 | 79.9 |
10 | 14/0.15 | 0.4 | 0.8 | 7.8 | 79.9 |
12 | 14/0.15 | 0.4 | 0.8 | 8.1 | 79.9 |
14 | 14/0.15 | 0.4 | 0.8 | 8.2 | 79.9 |
|
0.34mm2 |
No. of Cores | Conductor Construction (mm) | Insulation Thickness (mm) | Sheath Thickness (mm) | Overall Diameter (mm) | Max. DCR at 20ºC (Ω/km) |
2 | 20/0.15 | 0.4 | 0.7 | 5.2 | 57 |
3 | 20/0.15 | 0.4 | 0.7 | 5.5 | 57 |
4 | 20/0.15 | 0.4 | 0.7 | 5.9 | 57 |
5 | 20/0.15 | 0.4 | 0.7 | 6.3 | 57 |
7 | 20/0.15 | 0.4 | 0.7 | 6.8 | 57 |
8 | 20/0.15 | 0.4 | 0.8 | 7.5 | 57 |
10 | 20/0.15 | 0.4 | 0.8 | 8.6 | 57 |
12 | 20/0.15 | 0.4 | 0.8 | 9.1 | 57 |
14 | 20/0.15 | 0.4 | 0.8 | 9.5 | 57 |
|
0.5mm2 |
No. of Cores | Conductor Construction (mm) | Insulation Thickness (mm) | Sheath Thickness (mm) | Overall Diameter (mm) | Max. DCR at 20ºC (Ω/km) |
2 | 16/0.20 | 0.45 | 0.7 | 5.6 | 39 |
3 | 16/0.20 | 0.45 | 0.7 | 6 | 39 |
4 | 16/0.20 | 0.45 | 0.7 | 6.4 | 39 |
5 | 16/0.20 | 0.45 | 0.7 | 6.9 | 39 |
7 | 16/0.20 | 0.45 | 0.8 | 7.6 | 39 |
8 | 16/0.20 | 0.45 | 0.8 | 8.2 | 39 |
10 | 16/0.20 | 0.45 | 0.8 | 9.8 | 39 |
12 | 16/0.20 | 0.45 | 0.8 | 10.2 | 39 |
14 | 16/0.20 | 0.45 | 0.9 | 10.6 | 39 |
|
0.75mm2 |
No. of Cores | Conductor Construction (mm) | Insulation Thickness (mm) | Sheath Thickness (mm) | Overall Diameter (mm) | Max. DCR at 20ºC (Ω/km) |
2 | 24/0.20 | 0.5 | 0.8 | 6.4 | 26 |
3 | 24/0.20 | 0.5 | 0.8 | 6.8 | 26 |
4 | 24/0.20 | 0.5 | 0.8 | 7.3 | 26 |
5 | 24/0.20 | 0.5 | 0.8 | 7.9 | 26 |
7 | 24/0.20 | 0.5 | 0.8 | 8.5 | 26 |
8 | 24/0.20 | 0.5 | 0.9 | 9.4 | 26 |
10 | 24/0.20 | 0.5 | 0.9 | 11 | 26 |
12 | 24/0.20 | 0.5 | 0.9 | 11.4 | 26 |
14 | 24/0.20 | 0.5 | 1 | 12.1 | 26 |
|
1.0mm2 |
No. of Cores | Conductor Construction (mm) | Insulation Thickness (mm) | Sheath Thickness (mm) | Overall Diameter (mm) | Max. DCR at 20ºC (Ω/km) |
2 | 32/0.20 | 0.6 | 0.8 | 7.2 | 19.5 |
3 | 32/0.20 | 0.6 | 0.8 | 7.7 | 19.5 |
4 | 32/0.20 | 0.6 | 0.8 | 8.3 | 19.5 |
5 | 32/0.20 | 0.6 | 0.8 | 9.2 | 19.5 |
7 | 32/0.20 | 0.6 | 0.9 | 10.3 | 19.5 |
|
1.5mm2 |
No. of Cores | Conductor Construction (mm) | Insulation Thickness (mm) | Sheath Thickness (mm) | Overall Diameter (mm) | Max. DCR at 20ºC (Ω/km) |
2 | 30/0.25 | 0.6 | 0.8 | 7.8 | 13.3 |
3 | 30/0.25 | 0.6 | 0.8 | 8.4 | 13.3 |
4 | 30/0.25 | 0.6 | 0.8 | 9.2 | 13.3 |
5 | 30/0.25 | 0.6 | 0.9 | 10.2 | 13.3 |
7 | 30/0.25 | 0.6 | 1 | 11 | 13.3 |