Model NO.
All Aluminum Conductor-AAC
Application
Overhead, Underground
Conductor Material
Aluminum
Sheath Material
Bare Stranded Aluminium Conductor
Material Shape
Round Wire
Range of Application
Electric Transmission Line Overhead.
Certification
ISO9001, CCC, SABS
Conductor
Aluminium/Aluminum
Content of Aluminium
More Than 99.95%
Reference Standard
GOST 839-80
Specification
GOST 839-80
All Aluminium Conductor-AAC Conductor
APPLICATION
AAC conductor is also known as aluminium stranded conductor,This product is suitable for electric transmission line overhead
Type A Without Greased Type AKπ With Greased
CABLE STANDARDS
Enterprise Standards, National Standards, IEC,BS,AS,JIS,ASTM,DIN,AS/NZS,SANS and etc. upon request.
CONSTRUCTION-GOST Standard 839-1980
Nominal Cross-sectional Area(mm2) | Number Of Wire (mm) | Diameter (mm) | Appro.overall Diameter(mm) | Min. Breaking Load(N) | Max.D.C.resistance Of Conductor At 20ºC(Ω/km) | Appro.Weight-Type A(Kg/km) | Appro.Weight of Greased Type AKπ(Kg/km) |
10 | 7 | 1.35 | 4.05 | 1950 | 2.8631 | 27.4 | - |
16 | 7 | 1.70 | 5.10 | 3021 | 1.8007 | 43.0 | 0.5 |
25 | 7 | 2.13 | 6.40 | 4500 | 1.1498 | 68.0 | 0.5 |
35 | 7 | 2.50 | 7.50 | 5913 | 0.8347 | 94.0 | 0.5 |
40 | 7 | 2.70 | 8.09 | 6800 | 0.7157 | 109.4 | - |
50 | 7 | 3.00 | 9.00 | 8198 | 0.5784 | 135.0 | 0.5 |
63 | 7 | 3.39 | 10.16 | 10390 | 0.4544 | 172.3 | - |
70 | 7 | 3.55 | 10.70 | 11288 | 0.4131 | 189.0 | 1.0 |
95 | 7 | 4.10 | 12.30 | 14784 | 0.3114 | 252.0 | 1.0 |
100 | 19 | 2.59 | 12.94 | 17000 | 0.2877 | 274.9 | - |
120 | 19 | 2.80 | 14.00 | 19890 | 0.2459 | 321.0 | 16 |
125 | 19 | 2.89 | 14.47 | 21250 | 0.2301 | 343.6 | - |
150 | 19 | 3.15 | 15.80 | 24420 | 0.1944 | 406.0 | 20 |
160 | 19 | 3.27 | 16.37 | 26400 | 0.1798 | 439.8 | - |
185 | 19 | 3.50 | 17.50 | 29832 | 0.1574 | 502.0 | 25 |
200 | 19 | 3.66 | 18.30 | 32000 | 0.1438 | 549.7 | - |
240 | 19 | 4.00 | 20.00 | 38192 | 0.1205 | 655.0 | 33 |
250 | 19 | 4.09 | 20.47 | 40000 | 0.1150 | 687.1 | - |
ALL Aluminium Conductor-AAC(GOST Standard 839-1980)
Nominal Cross-sectional Area(mm2) | Number Of Wire (mm) | Diameter (mm) | Appro.overall Diameter(mm) | Min. Breaking Load(N) | Max.D.C.resistance Of Conductor At 20ºC(Ω/km) | Appro.Weight- Type A(Kg/km) | Appro.Weight of Greased Type AKπ(Kg/km) |
300 | 37 | 3.29 | 22.10 | 47569 | 0.1000 | 794.0 | 54 |
315 | 37 | 3.29 | 23.05 | 51970 | 0.0915 | 867.5 | - |
350 | 37 | 3.45 | 24.20 | 57057 | 0.0833 | 952.0 | 65 |
400 | 37 | 3.66 | 25.60 | 63420 | 0.0740 | 1072.0 | 73 |
450 | 37 | 3.90 | 27.30 | 71856 | 0.0642 | 1206.0 | 84 |
500 | 37 | 4.15 | 29.10 | 80000 | 0.0576 | 1378.0 | 94 |
550 | 37 | 3.37 | 30.30 | 89760 | 0.0529 | 1500.0 | 117 |
560 | 37 | 4.39 | 30.73 | 89600 | 0.0531 | 1542.2 | - |
600 | 61 | 3.50 | 31.50 | 95632 | 0.0491 | 1618.0 | 126 |
630 | 61 | 3.63 | 32.64 | 100800 | 0.0458 | 1738.4 | - |
650 | 61 | 3.66 | 32.90 | 104575 | 0.0450 | 1771.0 | 138 |
700 | 61 | 3.80 | 34.20 | 112725 | 0.0417 | 1902.0 | 149 |
710 | 61 | 3.85 | 34.65 | 113600 | 0.0406 | 1959.2 | - |
750 | 61 | 3.95 | 35.60 | 119584 | 0.0386 | 2062.0 | 161 |
*Other size can be provided as your requirement