Material Shape
Round Wire
Range of Application
Cold-Resistant
Certification
ISO9001, CE, CCC, RoHS, VDE
Voltage
3.6/6kv and 6/10kv
Standard
VDE0250 Part 605
Color
Black or as Request
Operating Temperature
-40 Degree to 80 Degree
Transport Package
500m 1000m Per Drum
(N)3GHSSHCH
8.7/15kV and 12/20kV
Cable specificationPhase Conductor
Class 5 copper conductor according to VDE 0295
(IEC 60228)
Insulation
Rubber compound conductor Type 3GI3 according to
VDE 0207 Part 20
Semi-Conductive Layers
Semi-conductive tape over the conductor and inner and outer
semi-conductive rubber layer on the insulation
Protective Earth Conductor
Individual copper screen
Control Conductor
Class 5 tinned copper according to VDE 0295 (IEC 60228)
Central Filler
Rubber compound on a textile polyester support
First Inner Sheath
LSZH (Low Smoke Zero Halogen) Type M1 according to
EN 50363
Monitoring Conductor
Copper wire screen over the first inner sheath
Second Inner Sheath
LSZH (Low Smoke Zero Halogen) Type M1 according to EN
50363
Armour
Steel wire braid over the second inner sheath
Outer Sheath
LSZH (Low Smoke Zero Halogen) Type M1 according to EN
50363
CHARACTERISTICS
Voltage Rating (Uo/U)
8.7/15kV
12/20kV
Test Voltage
8.7/15kV: 24kV
12/20kV: 29kV
Maximum Short Circuit Temperature
+250°C
Ambient Temperature
Fixed: -40°C to +80°C
Flexed: +5°C to +80°C
Bending Radius
Fixed: 6 x overall diameter
Flexed: 10 x overall diameter
Maximum Tensile Load*
15N/mm2
Sheath Colour
Black
CERTIFICATE
PRODUCTION LINE AND TEST EQUIPMENTPACKAGE