Purchase Qty. / Reference FOB Price |
---|
Production Capacity: | |
---|---|
Payment Terms: | LC, T/T |
BS EN 60702 Part 1 ,BS6387-2013,BS EN/IEC 60754,BS EN/IEC 61034, BS EN/IEC 60332 , BS EN/IEC 60331, IEC60502,BS7870-5
Mineral Insulated 500V Fire Resistance high temperature Cable APPLICATION :
750V heavy duty mineral insulated cable, designed to give the ultimate Fire Performance. Suitable for Oil, Gas and Petroleum
industries, airports, emergency lighting systems and fire alarm systems for power and control circuits providing circuit integrity
to 950°C.
Mineral Insulated 500V Fire Resistance high temperature Cable Structure:
Stranded Copper Conductor, Magnesium Oxide , Corrugated Copper Sheath
Test Method forMineral Insulated 500V Fire Resistance high temperature Cable:
Test Item | YTTW |
Refractory Test | Class S 950ºC 180Mins |
Spray Test | Class W 650ºC first burning 15 Mins and then burning and spray for 15 Mins |
Impact Test | Class Z 950ºC 30times in 15Mins |
Mineral Insulated 500V Fire Resistance high temperature Cable Technical Data:
Conductor: Stranded Copper Conductor Class 2
Operating voltage: 500V
Test Voltage: 2000V
Working Temperature:-5-250 º C
High temperature resistance:950 º C for 3 hours
Minimum bending radius: 6 x Overall Diameter,
Mineral Insulated 500V Fire Resistance high temperature Cable Character:
High temperature and fire resistance,can bear 950ºC burning for 3 hours.
Continous length can reach 2000M
Same fire proof class for joint
Multi-core available
High Overload capacity
Flexible
Easy Installation
enviorment protection
Moisture and Radiation Resistance,no electromagnetic interference when energized
Model of Mineral Insultated Cable
Model | Description | Voltage | Core | Nom.Cross sectional area mm2 |
YTTW | Strand Copper conductor,inorganic insulation copper sheath flexible fireproof cable | 500/750V | 1-4 | 1-300 |
YTTWV | Strand Copper conductor,inorganic insulation copper sheath PVC Outer sheath flexible fireproof cable | |||
DW-YTTWY | Strand Copper conductor,inorganic insulation copper sheath LSFH Outer sheath flexible fireproof cable |
Cable Parameter:
NO. OF CORES×NOMINAL CROSS SECTIONAL AREANOMINAL | NOMINAL OVERALL DIAMETER | NOMINAL WEIGHT | MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC |
No×mm² | mm | kg/km | ohms/km |
500V | |||
2×1 | 5.1 | 105 | 18.1 |
2×1.5 | 5.7 | 131 | 12.1 |
2×2.5 | 6.6 | 180 | 7.41 |
2×4 | 7.7 | 262 | 4.61 |
3×1 | 5.8 | 136 | 18.1 |
3×1.5 | 6.4 | 168 | 12.1 |
3×2.5 | 7.3 | 222 | 7.41 |
4×1 | 6.3 | 162 | 18.1 |
4×1.5 | 7 | 203 | 12.1 |
4×2.5 | 8.1 | 286 | 7.41 |
7×1.5 | 8.4 | 310 | 12.1 |
7×2.5 | 9.7 | 433 | 7.41 |