1 Product Standard This product is manufactured according to GB/T12706.1, equivalent to IEC60502.1. Or BS, DIN, ICEA standard as customer request.
2 Application The product is suitable for power transmission and distribution lines with rated powerfrequency voltage up to and including 0.6/1KV. Operating Performance 1). Rated power frequency voltage Uo/U: 0.6/1KV. 2). Max. Permissible continuous operating temperature of conductor: 70ºC 3). Max. Short-circuit temperature of the conductor shall not exceed: (5S maximum duration) 250ºC 4). The ambient temperature under installation should not below 0ºC 5). The bending radius of a cable should not be less than 15 times of the cable diameter. 6). The test voltage (A.C.): 3.5kV/5min. 7). The flame-retardant properties of cable comply with grade A, B, C of GB/T19666-2005 or IEC60332.
3 Construction:
Conductor:Solid or stranded copper,aluminum
Insulation: PVC
Circuit Identification:The insulation shall be red, black
Filler: Polypropylene lament with lapped binding tape