Conductor Type
Rigid Conductor
Application
System Connection Wire
Conductor Material
Rigid Conductor
Material Shape
Round Wire
Range of Application
System Connection Wire
Certification
ISO9001, CE, CCC
Armoured Layer
Steel Wire
Specification
CE, CCC, ISO
1,APPLICATION
Copper Conductor PVC Insulated Steel Wire Armoured PVC Sheathed Rigid Control Cable(KVV32) is mainly used for system connection wire of control,signal,protection or measuring for rated voltage up to and including 450/750V.
2,BASIC INFORMATION
Code Name
KVV32
Rated Voltage (Uo/U)
450/750V
Cable Structure
CU/PVC Insulation/Steel Wire Armoured/PVC Sheathed
3,CONSTRUCTION
Conductor
Preferred Number of cores:
2,3,4,5,7,8,10,12,14,16,19,24,27,30,37,44,48,52,61
The conductors shall comply with the requirement given in IEC 60228 for class 1 or 2.
- class 1 for solid conductors;
- class 2 for stranded conductors.
Insulation
PVC(Polyvinyl Chloride) Type PVC/A according to IEC
Armoured
Steel Wire
Sheathed
PVC(Polyvinyl Chloride) Type PVC/ST1 according to IEC
Other special application cable can be provided upon requests:
Fire-resistant,Flame-retardant,Low-halogen,Non-halogen,Low-fume,Low-smoke,as well as acid-alkali-proof,High temperature resistant,Termite and Rodent resistant,Water proof series and so on.
4,CABLE STANDARDS
GB/T,JB/T,IEC,BS,DIN,ICEA up on request.
5,CHARACTERISTICS
Conductor temperature
Maximum conductor temperature in normal use: 70ºC
Installation temperature
Ambient temperature under installation shall not be below 0ºC
Max.temperature of conductor under short circuit
-(Max.Duration 5 sec.)
PVC Insulated:160ºC
Preferred Permissible bending radius
For non-armoured PVC insulated cable not less than: 12 times of cable diameter
6,Production Scope Of Control Cable(KVV32)
Type | Nominal Cross Sectional Area of Conductor(mm2) |
KVV32 | 0.5 | 0.75 | 1.0 | 1.5 | 2.5 | 4 | 6 | 10 |
No. of Cores |
/ | 19~61 | 7~61 | 4~14 | 4~10 |
Note:Other your requirement can be provided by JiangNan Cable.
7,Dimensions And D.C Resistance-PVC Insulated Control Cable(KVV32)
Nominal Cross Sectional Area of Conductor(mm2) | Class of conductor | Max.D.C.Resistance at 20ºC(Ω/km) |
Plain | Metal-coated |
0.75 | 1 | 24.5 | 24.8 |
1.0 | 1 | 18.1 | 18.2 |
1.5 | 1 | 12.1 | 12.2 |
2.5 | 1 | 7.41 | 7.56 |
4 | 1 | 4.61 | 4.70 |
6 | 1 | 3.08 | 3.11 |
10 | 2 | 1.83 | 1.84 |