Model NO.
BS EN50525-3-11
Application
System Connection Wire
Conductor Material
Copper
Range of Application
System Connection Wire
Certification
ISO9001, CE, CCC, BS
Name
Armoured Control Cable,Mechanical Control Cable B
Specification
BSI, VDE, BS
APPLICATION
Used as interconnecting cable for measuring, controlling or regulation in control equipment for assembly and production lines,conveyors and for computer units. Suitable for fixed installationsor for flexible use when temporarily moved, and in conditions of medium mechanical stress. Can be used outdoors when protected, and in dry or damp conditions indoors.
BASIC INFORMATION
Code Name
SY LSZH
Rated Voltage (Uo/U)
300/500V
Cable Structure
Flexible CU/LSZH Polyolefin/LSZH Polyolefin/GSWB/ LSZH Polyolefin Sheath
CONSTRUCTION
Conductor
Preferred Number of cores:
2-5
The conductors shall comply with the requirement given in BS EN 60228(previously BS 6360) for class 5
- class 5 for Flexible conductors;
Insulation
Low Smoke Zero Halogen Polyolefin Similar with Type TI6 according to BS EN 50363
Beding
LSZH(Low Smoke Zero Halogen) Polyolefin Type TM7 according to BS EN 50363
Screen/Braiding
GSWB (Galvanized Steel Wire Braid)
Sheathed
LSZH(Low Smoke Zero Halogen) Polyolefin Type TM7 according to BS EN 50363
CABLE STANDARDS
GB/T,IEC,BS EN 50525-3-11(previously BS 6500),VDE up on request.
The electrical and dimensional properties of this product are measured by the Technical and Quality Assurance department at the JiangNan Cables laboratory. Cable performance in respect of conductor resistance, construction quality (workmanship), dimensional consistency, and other parameters are verified to published standards and approved product drawings. Conformance to RoHS (Restriction of the use of Hazardous Substances) is determined and confirmed.
CHARACTERISTICS
Installation temperature
Ambient temperature under installation shall not be below 0ºC
Temperature Rating
Fixed: -15°C to +70°C
Sheath Color: Black
Production Scope Of Control Cable(SY LSZH / BS EN 50525-3-11)
No. of Cores | Nominal Cross Sectional Area | Thickness of Insulation | Thickness of Bedding | Diameter of GSWB | Thickness of Sheath | Nominal Overall Diameter | Nominal Weight |
mm² | mm | mm | mm | mm | mm | kg/Km |
2 | 1.5 | 0.50 | 0.50 | 0.24 | 0.8 | 8.2 | 109 |
3 | 1 | 0.50 | 0.50 | 0.24 | 1.0 | 8.3 | 114 |
3 | 1.5 | 0.50 | 0.50 | 0.24 | 1.0 | 9.0 | 138 |
3 | 2.5 | 0.60 | 0.50 | 0.24 | 1.0 | 10.3 | 188 |
3 | 4 | 0.60 | 0.60 | 0.24 | 1.0 | 11.7 | 256 |
3 | 6 | 0.70 | 0.60 | 0.24 | 1.1 | 13.6 | 352 |
4 | 1.5 | 0.50 | 0.50 | 0.24 | 1.0 | 9.6 | 161 |
4 | 2.5 | 0.60 | 0.50 | 0.24 | 1.0 | 11.1 | 223 |
4 | 4 | 0.60 | 0.60 | 0.24 | 1.0 | 12.7 | 310 |
4 | 6 | 0.70 | 0.60 | 0.24 | 1.1 | 14.8 | 430 |
5 | 1.5 | 0.50 | 0.50 | 0.24 | 1.0 | 10.4 | 189 |
5 | 2.5 | 0.60 | 0.60 | 0.24 | 1.0 | 12.0 | 264 |
5 | 6 | 0.70 | 0.60 | 0.24 | 1.2 | 16.3 | 523 |
5 | 10 | 0.80 | 0.80 | 0.30 | 1.2 | 20.0 | 822 |
5 | 16 | 0.90 | 0.80 | 0.30 | 1.4 | 23.9 | 1217 |
D.C Resistance- Control Cable(SY LSZH / BS EN 50525-3-11)
Nominal Cross Sectional Area of Conductor(mm2) | Maximum Diameter Of Wires In Conductor(mm) | Max.D.C.Resistance Of Conductor at 20ºC- Plain Wires(Ω/km) |
1 | 0.21 | 19.5 |
1.5 | 0.26 | 13.3 |
2.5 | 0.26 | 7.98 |
4 | 0.31 | 4.95 |
6 | 0.31 | 3.3 |
10 | 0.41 | 1.91 |
16 | 0.41 | 1.21 |