Material Shape
Round Wire
Range of Application
Overhead
Certification
ISO9001, CE, UL, CCC
Delivery Length
Accord with The Request
Delivery Time
5~15 Official Days
Transport Package
Wooden Drum
single core 0.6/1kV Copper core PVC insulation overhead cable
1.Executive Standard GB/T12527-2008
2.Application:
This product is suitable for copper core,alumininum core or alumininum alloy core weatherproof PVC,PE and XLPE insulated overhead cable under AC rated voltage of 1KV in overgead power line.
3.Condition Of Usage
-The rated voltage U0/U0.6/1kV
-Admissible long-term operating temperature for conductor of cable For PVC and PE insulated ,not exceed 70ºC. For XLPE insulation ,not eceed 90 ºC.
-The temperature should not less than -20ºC during laying cable.
-Admissible bending radius:
For O.D.<25mm,the bending radius should not less than 4D.
For O.D.≥25mm,should not less than 6D.
4.Meaning Of Alphabets In Type
JK----refer to overhead LH----alumininum alloy
YJ----XLPE insuladed L----Alumininum
Y----Polyethylene insulation
Type | Description | Main Usage |
|
JKV-0.6/1 | Rated voltage 0.6/1kV Cu core PVC insulation overhead cable | Aerial fixed laying outgoing line etc |
|
JKLV-0.6/1 | Rated voltage 0.6/1kV Al core PVC insulation overhead cable |
|
JKLHV-0.6/1 | Rated voltage 0.6/1kV alloy core PVC insulation overhead cable |
|
JKY-0.6/1 | Rated voltage 0.6/1kV Cu core PE insulation overhead cable |
|
JKLY-0.6/1 | Rated voltage 0.6/1kV Al core PE insulation overhead cable |
|
JKLHY-0.6/1 | Rated voltage 0.6/1kV AL alloy core PE insulation overhead cable |
|
JKYJ-0.6/1 | Rated voltage 0.6/1kV Cu core XLPE insulation overhead cable |
|
JKLYJ-0.6/1 | Rated voltage 0.6/1kV Al core XLPE insulation overhead cable |
|
JKLHYJ-0.6/1 | Rated voltage 0.6/1kV AL alloy core XLPE insulation overhead cable |
|
Nominal Cross Section mm2 | The Resistance 20ºC≤Ohm/km | At Rated Work temperture the Lowest Insulation Resistance MΩ.km | Cable Drawing pressure ≥N |
|
Cu Core | Al Core | Al alloy Core |
|
Hard Cu | Soft Cu | 70ºC | 90ºC | Hard Cu Core | Al Core | Al alloy Core |
|
10 | 1.906 | 1.83 | 3.08 | 3.574 | 0.0067 | 0.0067 | 3471 | 1650 | 2514 |
16 | 1.198 | 1.15 | 1.91 | 2.217 | 0.0065 | 0.0065 | 5486 | 2512 | 4022 |
25 | 0.749 | 0.727 | 1.20 | 1.393 | 0.0054 | 0.0054 | 8465 | 3762 | 6284 |
35 | 0.54 | 0.524 | 0.868 | 1.007 | 0.0054 | 0.0054 | 11731 | 5177 | 8800 |
50 | 0.399 | 0.387 | 0.641 | 0.744 | 0.0046 | 0.0046 | 16502 | 7011 | 12569 |
70 | 0.276 | 0.268 | 0.443 | 0.514 | 0.0040 | 0.0040 | 23461 | 10354 | 17596 |
95 | 0.199 | 0.193 | 0.320 | 0.371 | 0.0039 | 0.0039 | 31759 | 13727 | 23880 |
120 | 0.158 | 0.153 | 0.253 | 0.294 | 0.0035 | 0.0035 | 39911 | 17339 | 30164 |
150 | 0.128 | 0.124 | 0.206 | 0.239 | 0.0035 | 0.0035 | 49505 | 21033 | 37706 |
185 | 0.1021 | 0.0991 | 0.164 | 0.19 | 0.0035 | 0.0035 | 61846 | 26732 | 46503 |
240 | 0.0777 | 0.0754 | 0.125 | 0.145 | 0.0034 | 0.0034 | 79823 | 34679 | 60329 |
300 | - | - | 0.100 | 0.116 | 0.0033 | 0.0033 | - | 43349 | 75411 |
400 | - | - | 0.0778 | 0.0904 | 0.0032 | 0.0032 | - | 55707 | 100548 |
Structure And Weight Of Rated Voltage 1kV Single Core Overhead Cables
No. | Core ×Nominal Cross Section mm2 | Calculating Diameter of Cable mm | Calculating Weight |
|
JKV | JKLV | JKY | JKLY | JKYJ | JKLYJ |
1 | 1×16 | 8.0 | 189.3 | 80.2 | 163.3 | 68.1 | 163.3 | 68.1 |
2 | 1×25 | 9.4 | 278.9 | 112.3 | 274.4 | 107.1 | 274.4 | 107.1 |
3 | 1×35 | 11.0 | 393.6 | 157 | 371.2 | 142.4 | 371.2 | 142.4 |
4 | 1×50 | 12.3 | 537.2 | 207.4 | 501.7 | 193.1 | 5011.7 | 193.1 |
5 | 1×70 | 14.1 | 753.2 | 280.2 | 708.9 | 259.7 | 708.9 | 259.7 |
6 | 1×95 | 16.5 | 1018.6 | 378.4 | 958.2 | 349.1 | 958.2 | 349.1 |
7 | 1×120 | 18.1 | 1226.1 | 464.4 | 1180.8 | 420.8 | 1180.8 | 420.8 |
8 | 1×150 | 20.2 | 1299.8 | 482.1 | 1464.8 | 522.1 | 1464.8 | 522.1 |
9 | 1×185 | 22.5 | 1996.4 | 720 | 1816.8 | 647 | 1816.8 | 647 |
10 | 1×240 | 25.6 | 2803.2 | 936.8 | 2375.5 | 848.1 | 2375.5 | 848.1 |