Application
Construction Installation
Conductor Material
Copper
Range of Application
Flame Retardant
Certification
ISO9001, CE, CCC
Good Character
Fire Retardant
Twin and earth electrical cable
Application
Application: Domestic wiring cable. Can be installed in fixed installations in dry or damp premises clipped to surface, on trays or in free air where mechanical damage would not be an issue. Suitable for laying in conduit or trunking where mechanical protection is required.
Standards: BS 6004: 2000 Table 8 or Australia standard AS/NZS 5000.1
Conductor:
Plain copper conductors to BS EN 60228
Class 1 solid: 1.0mm² , 1.5mm² And 2.5mm²
Class 2 stranded: 4.0mm² , 6.0mm² , 10.0mm² And 16.0mm²
Circuit Protection Conductor (Earth):
Class 1 solid plain copper conductor: 1.0mm² , 1.5mm² And 2.5mm²
Class 2 stranded plain copper conductor: 4.0mm² , 6.0mm² , 10.0mm² And 16.0mm²
Insulation: PVC type TI 1 to BS EN 50363-3: 2005
Sheath: PVC (Polyvinyl Chloride) to BS 7655-4.2: 2000
Sheath Colour: Grey
Voltage Rating: 300/500V
Temperature Rating:
Max: +70° C
Short Circuit: 160° C
Minimum Bending Radius: 6 x overall diameter
Core Identification:
Single Core: Brown or Blue
Twin: Brown and Blue
Three Core: Brown, Black (centre core), Grey.
No. of Cores x Nominal Cross Sectional Area (mm2 )
Main Conductor Type
Normal Thickness of Insulation
(mm)
Normal Thickness of Jacket(mm)
Earth Conductor Area(mm2 )
Over Diameter of Cable (mm)
Approx. Mass Kg/100m
2C+E
1.0
Solid
0.6
0.9
1.0
8.9*4.2
7.74
1.5
Strand
0.6
0.9
1.5
9.9*4.5
8.86
2.5
Strand
0.7
1.0
2.5
11.8*5.4
13.68
2.5
Strand
0.7
1.0
2.5
12.2*5.4
14.03
4.0
Strand
0.8
1.1
2.5
13.9*6.3
18.65
6.0
Strand
0.8
1.1
2.5
15.0*6.9
23.04
10.0
Strand
1.0
1.2
4.0
18.3*8.3
36.05
16.0
Strand
1.0
1.3
6.0
21.0*9.5
51.46
3C+E
1.5
Strand
0.6
0.9
1.5
12.6*4.5
11.54
2.5
Strand
0.7
1.0
2.5
15.7*5.4
18.31
more flat wire information,welcome to contact us directly.