Conductor Type
Stranded & Solid
Application
Household,Building
Conductor Material
Copper
Sheath Material
Nylon & PVC
Range of Application
Household,Building
Certification
ISO9001, CE, CCC, VDE
APPLICATION
Copper Conductor PVC Insulated Nylon Sheathed Rigid Wire and Cable(BVN) is mainly used at Fixed-wiring for construction,electrical apparatus and switch.
BASIC INFORMATION
1. Code Name
BVN
2. Rated Voltage (Uo/U)
300/500V
3. Cable Structure
CU/PVC Insulation/Nylon Sheathed
CONSTRUCTION
1. Conductor
Number of conductors:1 or other your requirement.
The conductors shall comply with the requirement given in IEC 60228 for class 1 or 2.
- class 1 for solid conductors;
- class 2 for stranded conductors.
2. Insulation
PVC(Polyvinyl Chloride) Type PVC/C according to IEC
3. Sheathed
Nylon
CABLE STANDARDS
GB/T,JB/T,IEC,BS,DIN,ICEA up on request.
CHARACTERISTICS
1. Conductor temperature
Maximum conductor temperature in normal use: 70ºC
2. Installation temperature
Ambient temperature under installation shall not be below 0ºC
3. Nylon Cable's advantage
The product is provided with excellent thermal stability, better machanical strength, surface strength, thermal distortion resistance, impact strength,beneling strength,a brasion-resistane,chemical resistance and geg-lubrication,as well as better machineoil resistance and gusoline resistance, gelf-lubrication will make installation easier and help reducing wire damage in the course of conduit installation.
DIMENSIONS-Nylon Sheathed Cable(BVN)
Nominal Cross Sectional Area of Conductor(mm2) | Class of conductor | Nominal Insulation Thickness (mm) | Min.Thickness of nylon sheath(mm) | Max.Average Overall Diameter (mm) | Max.D.C.Resistance at 20ºC(Ω/km) | Min.Insulation Resistance at 70ºC(Ω/km) |
Plain | Metal-coated |
0.5 | 1 | 0.4 | 0.10 | 2.2 | 36.0 | 36.7 | 0.015 |
0.75 | 1 | 0.4 | 0.10 | 2.4 | 24.5 | 24.8 | 0.012 |
0.75 | 2 | 0.4 | 0.10 | 2.5 | 24.5 | 24.8 | 0.014 |
1 | 1 | 0.4 | 0.10 | 2.6 | 18.1 | 18.2 | 0.011 |
1 | 2 | 0.4 | 0.10 | 2.7 | 18.1 | 18.2 | 0.013 |