Model NO.
60227 IEC 05 (BV)
Application
Household,Building
Conductor Material
Copper
Sheath Material
Non-Sheathed
Material Shape
Round Wire
Range of Application
Household,Building
Certification
ISO9001, CCC, RoHS, CB,SABS
Class of Conductor
Class 1 Copper Conductor
Specification
CB, ROHS, SABS
APPLICATION
60227 IEC 05(BV) Single-core Non-sheathed Solid Conductor Cable For Internal Wiring.
It is also used in power installation, household electrical appliance, instrument,Telecommunications equipment, switch control, relay and instrumentation panels of power switchgear and for purposes such as internal connectors in rectifier equipment, motor starters and controllers.
BASIC INFORMATION
1. Code Name
60227 IEC 05
2. Rated Voltage (Uo/U)
300/500V
3. Cable Structure
CU/PVC Insulation
CONSTRUCTION
Conductor
Number of conductots:1
The conductors shall comply with the requirement given in IEC 60228 for class 1
- class 1 for solid conductors;
Insulation
PVC(Polyvinyl Chloride) Type PVC/C according to IEC
CABLE STANDARDS
IEC60227,BS,DIN,ICEA up on request.
CHARACTERISTICS
Conductor temperature
Maximum conductor temperature in normal use: 70ºC
Installation temperature
Ambient temperature under installation shall not be below 0ºC
Minimum bending radius
The bending radius of cable: (D-Diameter of cable)
D≤25mm------------------≥4D
D>25mm------------------≥6D
DIMENSIONS-60227 IEC 05(BV)
Nominal Cross Sectional Area of Conductor(mm2) | CENELEC Code | Class of conductor | Nominal Insulation Thickness (mm) | Max.Overall Diameter (mm) | Max.D.C.Resistance at 20ºC(Ω/km) | Min.Insulation Resistance at 70ºC(Ω/km) |
Plain | Metal-coated |
0.5 | H05V-U | 1 | 0.6 | 2.3 | 13.3 | 13.7 | 0.010 |
0.75 | 1 | 0.6 | 2.5 | 7.89 | 8.21 | 0.009 |
1 | 1 | 0.6 | 2.7 | 4.95 | 5.09 | 0.007 |