Conductor Type
Class 5 Flexible Conductor
Application
Household,Building
Conductor Material
Copper
Material Shape
Round Wire
Range of Application
Household,Building
Certification
ISO9001, CE, CCC, RoHS, CB,SABS
Code Name
60227 IEC 06(RV)
APPLICATION
60227 IEC 06(RV) Single-core Non-sheathed Flexible Cable For Internal Wiring.
It is also used in power installation, household electrical appliance, instrument,Telecommunications equipment, switch control, relay and instrumentation panels of power switchgear and for purposes such as internal connectors in rectifier equipment, motor starters and controllers.
BASIC INFORMATION
1. Code Name
60227 IEC 06
2. Rated Voltage (Uo/U)
300/500V
3. Cable Structure
Flexible CU/PVC Insulation
CONSTRUCTION
Conductor
Number of conductors:1
The conductors shall comply with the requirement given in IEC 60228 for class 5
Insulation
PVC(Polyvinyl Chloride) Type PVC/C according to IEC
CABLE STANDARDS
IEC60227,BS,DIN,ICEA up on request.
CHARACTERISTICS
1. Conductor temperature
Maximum conductor temperature in normal use: 70ºC
2. Installation temperature
Ambient temperature under installation shall not be below 0ºC
3. Minimum bending radius
The bending radius of cable: (D-Diameter of cable)
D≤25mm------------------≥4D
D>25mm------------------≥6D
DIMENSIONS-60227 IEC 06(RV)
Nominal Cross Sectional Area of Conductor(mm2) | CENELEC Code | Class of conductor | Nominal Insulation Thickness (mm) | Max.Overall Diameter (mm) | Max.D.C.Resistance at 20ºC(Ω/km) | Min.Insulation Resistance at 70ºC(Ω/km) |
Plain | Metal-coated |
0.5 | H05V-K | 5 | 0.6 | 2.5 | 39.0 | 40.1 | 0.013 |
0.75 | 5 | 0.6 | 2.7 | 26.0 | 26.7 | 0.011 |
1 | 5 | 0.6 | 2.8 | 19.5 | 20.0 | 0.010 |